The short answer: A safety switch, or RCD, protects people from electric shock by cutting the power within milliseconds when current leaks from a circuit, which can happen when a power point, wiring or appliance is faulty. RCD testing checks that each safety switch still does this, because a switch that has stopped working gives no protection. In Queensland, the business running a workplace must have its safety switches tested to the methods and intervals in AS/NZS 3760, under the Electrical Safety Regulation 2026. For offices, shops, restaurants and most other service workplaces, WorkSafe Queensland lists a push-button test every six months and an operating time test every two years for fixed safety switches.
What is RCD testing?
RCD testing is the scheduled testing of the residual current devices, or safety switches in a building, including portable safety switches. A safety switch turns off the electricity within milliseconds when it detects current leaking from a circuit. Queensland’s regulation splits them into type 1 safety switches, rated at 10mA or less, and type 2 safety switches, rated above 10mA and up to 30mA.
Each safety switch gets two tests. The push-button test is done by pressing the T or TEST button on the switch, and it shows whether the switch trips. The operating time test uses a test instrument to apply a set leakage current and measure how long the switch takes to cut the power. A type 2 safety switch should trip within 300 milliseconds and a type 1 within 40 milliseconds. The push-button test proves the switch trips. Only the operating time test shows how quickly. A device that trips at 320ms has passed the push-button test and failed the one that counts.
A safety switch only protects people if it is working properly. If pressing the test button doesn’t trip the switch, the switch is faulty. At a workplace, the regulation requires a faulty safety switch to be tagged with a warning straight away and taken out of use.
How often is RCD testing required in Queensland?
For most Queensland offices, retail and service premises, fixed RCDs need a push-button test every six months and an operating time test every two years. Manufacturing sites move to a 12-month operating time test, and construction sites need a push-button test monthly with a timed test every 12 months. Portable RCDs follow their own schedule, which is more frequent on construction sites and for office push-button tests..
The Electrical Safety Regulation 2026 (Qld) requires workplaces to test safety switches at the intervals set in AS/NZS 3760. The regulation commenced on 1 September 2026 and replaced the 2013 regulation, and WorkSafe Queensland says it made no changes to existing regulatory requirements. Any testing contract still quoting the 2013 regulation is out of date.
WorkSafe Queensland publishes the intervals by the type of work carried out on the premises:
- Office and service work with fixed RCDs: push-button test every 6 months, operating time test every 2 years
- Office work with portable RCDs: push-button test every 3 months, operating time test every 2 years
- Service work other than commercial cleaning with portable RCDs: push-button test every 6 months, operating time test every 2 years
- Manufacturing and amusement venues with fixed RCDs: push-button test every 6 months, operating time test every 12 months
- Construction with fixed RCDs: push-button test monthly, operating time test every 12 months
- Construction with portable RCDs: push-button test daily or before each use, with a timed test every 3 months
A single site can fall into more than one category. Selling goods from a shop is service work, but the regulation lists sorting, processing and packing food products as manufacturing work, so a supermarket that packs food out the back could have both. Test each area at the interval for the work done there. The walkthrough at the start of a testing program is where that gets settled.
Who is responsible for RCD testing?
The duty sits with the person conducting a business or undertaking (PCBU), and each business must ensure the safety switches at its workplace are tested. Whether a strata body corporate carries the same duty for common property depends on whether it conducts a business or undertaking, which isn’t clear-cut for purely residential schemes, so committees should confirm with their strata manager or a lawyer.
What happens during an RCD test
- Site walkthrough and register. Every RCD is located, numbered and recorded: board, circuit, type and rating. An existing register is checked against what is on the wall.
- Push-button test. Each device is tripped from the front and reset. A device that does not trip is tagged and taken out of service.
- Operating time test. A calibrated tester applies the rated residual current and records the trip time. The pass limit depends on the device type.
- Tagging and logging. Each device gets a durable tag showing the test date and next due date, and the result goes into the register.
- Report. You receive the inventory, pass and fail results, the calibration certificate for the test instrument, and the next due dates, formatted for a safety file, an insurer or a body corporate archive.
Why RCD testing matters for a business
- Safety. Safety switches save lives, but only if they work.
- Liability. Not testing safety switches as required breaches the regulation, which is linked to the electrical safety duty in section 30 of the Electrical Safety Act 2002.
What if an RCD fails the test?
A device that fails either test is replaced on the spot where possible. If the circuit cannot be left dead, the RCD is tagged out of service and a replacement is quoted the same visit. Failed fixed RCDs are replaced by a licensed electrician and the new device is tested.
Repeated failures across one board usually point to something else which calls for a condition assessment of the switchboard, electrical thermal imaging of the board and potential switchboard upgrade.
Frequently Asked Questions
Is RCD testing a legal requirement in Queensland?
Yes. The Electrical Safety Regulation 2026 (Qld) sets maximum intervals between safety switch tests at workplaces and requires that testing is done by a competent person and recorded. AS/NZS 3760 provides the test method. The regulation commenced on 1 September 2026 and carried the previous requirements over unchanged.
Does a body corporate need to test RCDs in common areas?
It depends on whether the body corporate conducts a business or undertaking, which isn’t clear-cut for purely residential schemes, so committees should confirm with their strata manager or a lawyer. Either way, testing is the only way to know common property safety switches still work. Terawatt runs scheduled common property testing for body corporate and strata committees across the Sunshine Coast, Moreton Bay and Brisbane North.
What records do I need to keep for RCD testing?
A register listing each device, its location and rating, the date and result of each push-button and operating time test, the instrument calibration certificate, and the next due date. Keep it with the site safety file. Terawatt holds a register of test due dates and sends reminders when the next test falls due.
Need your RCDs tested and the records kept properly? Terawatt runs scheduled RCD testing Sunshine Coast wide for commercial and body corporate sites, as well as RCD testing in Brisbane and Moreton Bay. Call 1300 426 081 or book a site walkthrough.
About the author
Seth Atkinson, Director, Terawatt
Seth Atkinson leads Terawatt, the Sunshine Coast electrical contractor his father Keith founded in 1978. Terawatt holds Electrical Contractor Licence 84790 and Gold Master Electrician accreditation, and delivers commercial, strata, and body corporate electrical work, compliance testing and EV charging infrastructure across the Sunshine Coast, Moreton Bay and Brisbane North.